Watts 0063010

Watts 009M2 Ārai Rere Whakamuri Rohe Pēhanga Whakaiti (Tauira 0063010) Pukapuka Tohutohu

For Models: 009M2, 009M2-QT

1. Kupu Whakataki

This manual provides detailed instructions for the installation, operation, and maintenance of the Watts 009M2 Reduced Pressure Zone (RPZ) Backflow Preventer. This device is designed to protect potable water supplies from contamination due to backpressure or backsiphonage from non-potable sources. It is crucial to read and understand all instructions before installation and use to ensure proper function and safety.

The Watts 009M2 RPZ assembly features a compact, modular design for easy maintenance, with a single access cover for in-line repairs. It is suitable for continuous pressure piping applications and cross-connections identified as health hazards.

2. Nga Korero Haumaru Nui

3. Hua Neke Atuview me nga Waehanga

The Watts 009M2 Reduced Pressure Zone Backflow Preventer is constructed with a durable bronze body and features NPT end connections. Key components include:

Watts 009M2 Reduced Pressure Zone Backflow Preventer
Figure 1: Watts 009M2 Reduced Pressure Zone Backflow Preventer. This image shows the bronze body, quarter-turn shutoff valves with green handles, and multiple test cocks on top.

4. Tatūnga me te Tāuta

  1. Taki o mua-Tāuta:
    • Verify that the product model (009M2) and size (2 inch) match your requirements.
    • Tirohia te waeine mō ngā pakaru tuku.
    • Ensure all necessary tools and materials for installation are available.
  2. Whakaritenga Pae:
    • Choose an installation location that allows for easy access for testing and maintenance.
    • Ensure adequate drainage for the relief valve discharge.
    • The device should be installed horizontally, with the relief valve pointing downwards.
  3. Hononga paipa:
    • Flush the upstream piping thoroughly to remove any debris before connecting the backflow preventer.
    • Connect the inlet and outlet piping to the NPT connections on the device. Use appropriate thread sealant.
    • Avoid overtightening connections to prevent damage to the bronze body.
    • Ensure the flow arrow on the device body matches the direction of water flow.
  4. Relief Valve Drain:
    • Connect a drain line to the relief valve outlet. The drain line must be adequately sized and sloped to allow for free discharge and prevent backpressure on the relief valve.
    • Ensure the drain line terminates in an air gap, preventing any possibility of cross-connection.
  5. Taki i muri-Tāutatanga:
    • Slowly open the upstream shutoff valve, then the downstream shutoff valve, to gradually fill the system and prevent water hammer.
    • Tirohia nga hononga katoa mo te turuturu.
    • Perform initial testing by a certified backflow prevention tester to ensure proper operation and compliance with local codes.

5. Nga Tohutohu Whakahaere

The Watts 009M2 is designed for continuous pressure operation. Normal operation involves the device being fully open, allowing water to flow through the system while providing backflow protection.

6. Tiaki

Regular maintenance is critical for the reliable performance of your backflow preventer. The modular design and single access cover simplify servicing.

7. Te Raru

RaruraruTake peaRongoā
Water discharge from relief valve (continuous)
  • Fouled first check valve
  • Damaged relief valve seat or disc
  • Excessive backpressure
  • Clean or repair first check valve.
  • Inspect and replace relief valve components.
  • Identify and correct source of backpressure.
No water flow or reduced flow
  • Shutoff valves closed
  • Debris obstructing flow
  • Fouled check valves
  • Ensure shutoff valves are fully open.
  • Isolate and inspect for debris.
  • Clean or repair check valves.
Nga pakaru mai i nga hononga
  • Improperly sealed threads
  • Damaged gaskets
  • Re-apply thread sealant and tighten connections.
  • Tirohia me te whakakapi i ngā gaskets.

For issues not listed or if troubleshooting steps do not resolve the problem, contact a certified plumbing professional or Watts technical support.

8. Whakatakotoranga

Tau tauira0063010 (009M2)
Backflow Preventer TypeHuihuinga Rohe Pehenga Whakaiti
Rauemi tinanaParahi
Inlet/Outlet Connection Size2 Inches (50 MM)
Inlet/Outlet Connection TypeFemale Threaded NPT
Te Morahi Mahi Mahi175 PSI (12.10 BAR)
Paemahana Morahi180°F (82°C)
Temperature Iti33°F (0.5°C)
Momo TiakiBackpressure and Backsiphonage
Rahi Hua (L x W x H)22 x 10 x 8 inihi
Taumaha Tūemi27 Pauna
Lead Free StatusNO (For non-potable use only)

9. Pūtāhui me te Tautoko

Specific warranty information for Watts products is typically provided with the product packaging or available on the official Watts website. Please refer to these resources for the most current warranty terms and conditions.

Mō te tautoko hangarau, ngā wāhanga whakakapinga, ētahi atu āwhina rānei, whakapā atu ki te ratonga kiritaki a Watts, toro atu rānei ki tā rātou paetukutuku mana website. Ensure you have your product model number (0063010) and serial number (if applicable) ready when contacting support.

Watts Official Webpae: www.watts.com

Tuhinga e pa ana - 0063010

Preview Watts LF909 Series Whakaitihia te Pehenga Rohe Huihuinga Huihuinga Hangarau Hangarau
Whakatakotoranga hangarau mo te Watts LF909 Series Reduced Pressure Zone Assembly (21⁄2" - 10"). Taipitopito āhuatanga, mahi, rawa, inenga, me te kaha mo tenei taputapu arai rerenga whakamuri Lead Free me te pūoko waipuke.
Preview Watts Raupapa 009, LF009, LFU009, SS009, U009: Pukapuka Tāutanga, Tiaki, me te Whakatikatika
This comprehensive manual from Watts provides essential guidance for the installation, maintenance, and repair of the Series 009, LF009, LFU009, SS009, and U009 Reduced Pressure Zone Assemblies. It details safety warnings, installation procedures, inspection, servicing, troubleshooting, and warranty information for these critical backflow prevention devices.
Preview Pukapuka Tāutanga, Tiaki, me te Whakatikatika mō ngā Huihuinga Rohe Pēhanga Iti o Watts Raupapa 909, LF909, 909RPDA
Comprehensive guide for the installation, maintenance, and repair of Watts Series 909, LF909, and 909RPDA Reduced Pressure Zone Assemblies, including safety warnings, installation guidelines, testing procedures, servicing instructions, troubleshooting, and warranty information.
Preview Ngā Huihuinga Rohe Pēhanga Whakaitihia o Watts Series LF909 - Whakatakotoranga Hangarau
Ngā whakatakotoranga hangarau taipitopito mō ngā Watts Series LF909 Reduced Pressure Zone Assemblies, tae atu ki ngā āhuatanga, te mahi, ngā ine, ngā taumaha, me te kaha. I hangaia mō te whakahaere hononga whakawhiti wai inu.
Preview Pukapuka Tāutanga, Tiaki, me te Whakatikatika mō ngā Huihuinga Rohe Pēhanga Iti o Watts Raupapa 009, LF009, LFU009, SS009, U009
Comprehensive guide for the installation, maintenance, and repair of Watts Series 009, LF009, LFU009, SS009, and U009 Reduced Pressure Zone Assemblies, covering safety, installation procedures, annual inspection, troubleshooting, and service. Includes details on flood sensor activation and connection kits.
Preview Watts Series LF919 Reduced Pressure Zone Assembly: Installation, Maintenance, and Repair Manual
Comprehensive guide for installing, maintaining, and repairing the Watts Series LF919 Reduced Pressure Zone Assembly (1/2" - 2"). Includes safety warnings, installation procedures, servicing instructions, and troubleshooting.