Danfoss 034L0097

Danfoss KVR15 Pressure Regulator Instruction Manual

Tauira: 034L0097

1. Kupu Whakataki

This manual provides essential information for the safe and efficient installation, operation, and maintenance of the Danfoss KVR15 Pressure Regulator. The KVR15 is designed to maintain a constant evaporating pressure in refrigeration and air conditioning systems. It features a 5/8 inch ODF connection and an access port for pressure measurement.

Please read this manual thoroughly before installing or operating the unit. Keep this manual for future reference.

2. Nga korero haumaru

WHAKATŪPATO: Mā te tāutanga, te whakahaere, te tiaki rānei kāore i te tika ka pā he whara kino, ka pakaru rānei ngā taputapu.

3. Ihirangi mokete

Manatokohia kei te noho katoa nga waahanga me te kore e pakaru i te wa e wetewete ana:

Danfoss KVR15 Pressure Regulator with 5/8 inch ODF connections and an access port

Image: Danfoss KVR15 Pressure Regulator. This image shows the compact design of the regulator, highlighting its 5/8 inch ODF connections on both ends and a small access port located on the side for pressure monitoring.

4. Tatūnga me te Tāuta

Follow these steps for proper installation of the KVR15 Pressure Regulator:

  1. Whakaritenga Pūnaha: Ensure the refrigeration system is depressurized and isolated before beginning installation.
  2. Tauwāhi: Install the regulator in the suction line, upstream of the compressor, and preferably in a horizontal pipe run. Ensure there is sufficient space for service and adjustment.
  3. Hononga: The KVR15 features 5/8 inch ODF (Outside Diameter Flare) connections. Use appropriate brazing techniques for copper tubing. Ensure the regulator is clean and free of debris before brazing. Protect the valve body from excessive heat during brazing by wrapping it with a wet cloth or using a heat sink compound.
  4. Aronga Rere: Observe the arrow on the regulator body, which indicates the correct flow direction. Install the regulator so that the refrigerant flows in the direction of the arrow.
  5. Tauranga Uru: The access port allows for pressure measurement. Ensure the cap is securely tightened after use to prevent leaks.
  6. Whakamātautau turuturu: After installation, perform a thorough leak test on all connections using an appropriate leak detection method.
  7. Whakaputaina: Evacuate the system to the required vacuum level before charging with refrigerant.

Utauta Manakohia: Brazing torch, nitrogen for purging, leak detector, vacuum pump, manifold gauge set, pipe cutters, deburring tool, wet rags or heat sink compound.

5. Nga Tohutohu Whakahaere

The KVR15 regulator is designed to maintain a constant evaporating pressure. Adjustment is typically performed during system commissioning.

  1. Tautuhinga Tuatahi: The regulator is factory set to a nominal pressure. For specific system requirements, adjustment may be necessary.
  2. Te Whakaritea Pehenga:
    • Remove the protective cap from the adjustment spindle.
    • Turn the adjustment spindle clockwise to increase the evaporating pressure.
    • Turn the adjustment spindle counter-clockwise to decrease the evaporating pressure.
    • Use a pressure gauge connected to the access port or elsewhere in the suction line to monitor the pressure while adjusting.
    • Make small adjustments and allow the system to stabilize before making further changes.
    • Once the desired pressure is achieved, replace and tighten the protective cap to secure the setting and prevent leaks.
  3. Access Port Usage: The access port allows for temporary connection of a pressure gauge to verify the regulated pressure. Always ensure the port cap is securely tightened when not in use.

6. Tiaki

The Danfoss KVR15 Pressure Regulator is designed for long-term, reliable operation with minimal maintenance. However, periodic checks are recommended.

Tuhipoka: Internal components of the KVR15 are not user-serviceable. If the regulator malfunctions, it should be replaced by a qualified technician.

7. Te Raru

This section provides solutions to common issues that may arise with the KVR15 Pressure Regulator.

RaruraruTake peaRongoā
Regulated pressure is too high/low.Incorrect adjustment setting.Adjust the regulator setting as described in the "Operating Instructions" section.
Pressure fluctuates significantly.System instability; debris in regulator; incorrect sizing.Check for system issues (e.g., TXV operation). If debris is suspected, the regulator may need replacement. Verify regulator sizing for the application.
Refrigerant leak at connections.Improper brazing; loose access port cap.Re-braze connections if necessary. Ensure access port cap is securely tightened.
No pressure regulation.Internal failure; completely clogged.The regulator may need to be replaced. Consult a qualified technician.

If troubleshooting steps do not resolve the issue, contact a qualified HVAC/R technician or Danfoss technical support.

8. Whakatakotoranga

ĀhuahiraTaipitopito
WaitohuDanfoss
Tau tauira034L0097
MomoEvaporating Pressure Regulator (KVR15)
Rahi Hononga5/8 inch ODF (Outside Diameter Flare)
Pūnaha IneInihi
Ngā āhuatangaTauranga Uru
KaihangaDanfoss
ASINB0085POK2G
Te Ra Tuatahi WāteaHakihea 27, 2017

9. Nga Korero Whakaputanga

Danfoss products are manufactured to high-quality standards. This product is covered by Danfoss's standard manufacturer's warranty. Specific warranty terms and conditions, including duration and coverage details, can be found on the official Danfoss website or by contacting Danfoss customer service. Please retain your proof of purchase for warranty claims.

Tuhipoka: The warranty may be voided by improper installation, unauthorized modifications, or use outside of specified operating conditions.

10. Tautoko Kiritaki

For technical assistance, spare parts, or further information regarding the Danfoss KVR15 Pressure Regulator, please visit the official Danfoss webpaetukutuku, whakapā atu rānei ki tā rātou tari tautoko kiritaki.

Danfoss Official Webpae: www.danfoss.com

When contacting support, please have your product model number (034L0097) and serial number (if applicable) ready.

Tuhinga e pa ana - 034L0097

Preview Danfoss ERC 214 Digital Regulator Installation Guide
Comprehensive installation guide for the Danfoss ERC 214 digital regulator, detailing its features, user interface, quick-start configuration, basic functions, technical data, and parameter settings for refrigeration and defrosting applications.
Preview Danfoss RT Series Pressure Switch Guide Installation
Ko tenei aratohu e whakarato ana i nga tohutohu whakaurunga mo nga huringa pehanga raupapa Danfoss RT, tae atu ki nga tauira RT 6W, RT 6B, RT 6S, RT 6AW, RT 6AB, RT 6AS, RT 30AW, RT 30AB, me RT 30AS. Kei roto i nga ahuatanga o nga hua, nga whakaritenga hangarau, nga tikanga whakauru, nga hononga hiko, me nga whakatikatika tautuhinga, me nga whakaaetanga mai i te EN 12263 me te tohu CE.
Preview Aratohu Tāutanga mō te Pātene Pēhanga Danfoss KPI 34, 35, 36, 38
Installation guide for Danfoss KPI series pressure switches (KPI 34, 35, 36, 38), detailing specifications, temperature limits, pressure ranges, differential settings, electrical ratings, and wiring instructions.
Preview Aratohu Tāutanga o te Pātene Pēhanga Rerekētanga Danfoss MP 54, MP 55, MP 55A
He aratohu tāutanga mō ngā pana pēhanga rerekētanga Danfoss MP 54, MP 55, me te MP 55A, e whakaatu ana i ngā taipitopito o te hototahitanga o te hauhautanga, ngā whakatakotoranga hangarau, me ngā tikanga tāutanga.
Preview Danfoss ERC 213 Te Aratohu Whakataunga Mana Whakaoho Hiko
Installation guide for the Danfoss ERC 213 electronic refrigeration controller, detailing its technical highlights, user interface, dimensions, electrical connections, and parameter settings for commercial refrigeration applications.
Preview Danfoss HFI Float Valve (High Pressure) - Installation and Maintenance Guide
Comprehensive guide for installing and maintaining the Danfoss HFI Float Valve (High Pressure). Covers refrigerant compatibility, temperature and pressure specifications, detailed installation steps including welding and assembly, tightening procedures, and maintenance tasks like purging and float assembly replacement. Includes safety notes and technical specifications.