1. Kupu Whakataki
This manual provides essential information for the safe and efficient installation, operation, and maintenance of the Danfoss KVR15 Pressure Regulator. The KVR15 is designed to maintain a constant evaporating pressure in refrigeration and air conditioning systems. It features a 5/8 inch ODF connection and an access port for pressure measurement.
Please read this manual thoroughly before installing or operating the unit. Keep this manual for future reference.
2. Nga korero haumaru
WHAKATŪPATO: Mā te tāutanga, te whakahaere, te tiaki rānei kāore i te tika ka pā he whara kino, ka pakaru rānei ngā taputapu.
- Only qualified personnel should install, service, or repair this equipment.
- Always depressurize the system before attempting any installation or maintenance.
- Mau taputapu whakamarumaru whaiaro (PPE) e tika ana, tae atu ki nga karaehe haumaru me nga karapu.
- Ensure all connections are properly sealed to prevent refrigerant leaks.
- Do not exceed the maximum operating pressure specified for the regulator.
- Refer to local regulations and standards for refrigerant handling and system installation.
3. Ihirangi mokete
Manatokohia kei te noho katoa nga waahanga me te kore e pakaru i te wa e wetewete ana:
- Danfoss KVR15 Pressure Regulator (Model: 034L0097)
- Pukapuka Tohutohu (tenei tuhinga)

Image: Danfoss KVR15 Pressure Regulator. This image shows the compact design of the regulator, highlighting its 5/8 inch ODF connections on both ends and a small access port located on the side for pressure monitoring.
4. Tatūnga me te Tāuta
Follow these steps for proper installation of the KVR15 Pressure Regulator:
- Whakaritenga Pūnaha: Ensure the refrigeration system is depressurized and isolated before beginning installation.
- Tauwāhi: Install the regulator in the suction line, upstream of the compressor, and preferably in a horizontal pipe run. Ensure there is sufficient space for service and adjustment.
- Hononga: The KVR15 features 5/8 inch ODF (Outside Diameter Flare) connections. Use appropriate brazing techniques for copper tubing. Ensure the regulator is clean and free of debris before brazing. Protect the valve body from excessive heat during brazing by wrapping it with a wet cloth or using a heat sink compound.
- Aronga Rere: Observe the arrow on the regulator body, which indicates the correct flow direction. Install the regulator so that the refrigerant flows in the direction of the arrow.
- Tauranga Uru: The access port allows for pressure measurement. Ensure the cap is securely tightened after use to prevent leaks.
- Whakamātautau turuturu: After installation, perform a thorough leak test on all connections using an appropriate leak detection method.
- Whakaputaina: Evacuate the system to the required vacuum level before charging with refrigerant.
Utauta Manakohia: Brazing torch, nitrogen for purging, leak detector, vacuum pump, manifold gauge set, pipe cutters, deburring tool, wet rags or heat sink compound.
5. Nga Tohutohu Whakahaere
The KVR15 regulator is designed to maintain a constant evaporating pressure. Adjustment is typically performed during system commissioning.
- Tautuhinga Tuatahi: The regulator is factory set to a nominal pressure. For specific system requirements, adjustment may be necessary.
- Te Whakaritea Pehenga:
- Remove the protective cap from the adjustment spindle.
- Turn the adjustment spindle clockwise to increase the evaporating pressure.
- Turn the adjustment spindle counter-clockwise to decrease the evaporating pressure.
- Use a pressure gauge connected to the access port or elsewhere in the suction line to monitor the pressure while adjusting.
- Make small adjustments and allow the system to stabilize before making further changes.
- Once the desired pressure is achieved, replace and tighten the protective cap to secure the setting and prevent leaks.
- Access Port Usage: The access port allows for temporary connection of a pressure gauge to verify the regulated pressure. Always ensure the port cap is securely tightened when not in use.
6. Tiaki
The Danfoss KVR15 Pressure Regulator is designed for long-term, reliable operation with minimal maintenance. However, periodic checks are recommended.
- Tirotiro Ataata: Periodically inspect the regulator and its connections for any signs of leaks, corrosion, or physical damage.
- Kitenga turuturu: Conduct regular leak checks on all brazed connections, especially around the regulator body and access port.
- Taki Taumahi: If system performance issues arise, verify that the regulator is maintaining the set pressure. This can be done by connecting a pressure gauge to the access port.
- Te horoi: Keep the exterior of the regulator clean. Do not use harsh chemicals that could damage the valve body or seals.
Tuhipoka: Internal components of the KVR15 are not user-serviceable. If the regulator malfunctions, it should be replaced by a qualified technician.
7. Te Raru
This section provides solutions to common issues that may arise with the KVR15 Pressure Regulator.
| Raruraru | Take pea | Rongoā |
|---|---|---|
| Regulated pressure is too high/low. | Incorrect adjustment setting. | Adjust the regulator setting as described in the "Operating Instructions" section. |
| Pressure fluctuates significantly. | System instability; debris in regulator; incorrect sizing. | Check for system issues (e.g., TXV operation). If debris is suspected, the regulator may need replacement. Verify regulator sizing for the application. |
| Refrigerant leak at connections. | Improper brazing; loose access port cap. | Re-braze connections if necessary. Ensure access port cap is securely tightened. |
| No pressure regulation. | Internal failure; completely clogged. | The regulator may need to be replaced. Consult a qualified technician. |
If troubleshooting steps do not resolve the issue, contact a qualified HVAC/R technician or Danfoss technical support.
8. Whakatakotoranga
| Āhuahira | Taipitopito |
|---|---|
| Waitohu | Danfoss |
| Tau tauira | 034L0097 |
| Momo | Evaporating Pressure Regulator (KVR15) |
| Rahi Hononga | 5/8 inch ODF (Outside Diameter Flare) |
| Pūnaha Ine | Inihi |
| Ngā āhuatanga | Tauranga Uru |
| Kaihanga | Danfoss |
| ASIN | B0085POK2G |
| Te Ra Tuatahi Wātea | Hakihea 27, 2017 |
9. Nga Korero Whakaputanga
Danfoss products are manufactured to high-quality standards. This product is covered by Danfoss's standard manufacturer's warranty. Specific warranty terms and conditions, including duration and coverage details, can be found on the official Danfoss website or by contacting Danfoss customer service. Please retain your proof of purchase for warranty claims.
Tuhipoka: The warranty may be voided by improper installation, unauthorized modifications, or use outside of specified operating conditions.
10. Tautoko Kiritaki
For technical assistance, spare parts, or further information regarding the Danfoss KVR15 Pressure Regulator, please visit the official Danfoss webpaetukutuku, whakapā atu rānei ki tā rātou tari tautoko kiritaki.
Danfoss Official Webpae: www.danfoss.com
When contacting support, please have your product model number (034L0097) and serial number (if applicable) ready.