Elitech EMG-40Vpro

Elitech EMG-40Vpro Intelligent HVAC Digital Manifold Gauge

Pukapuka Kaiwhakamahi

1. Hua Neke Atuview

The Elitech EMG-40Vpro is an intelligent digital manifold gauge system designed for HVAC and refrigeration professionals. It integrates multiple tools into one unit, providing real-time monitoring and analysis of vacuum, pressure, and temperature. The system includes a digital manifold, a wireless vacuum micron gauge (VGW-mini), and wireless temperature clamps (IPT-01) for comprehensive system diagnostics.

Elitech EMG-40Vpro Digital Manifold Gauge with accessories

Figure 1.1: Elitech EMG-40Vpro Digital Manifold Gauge, VGW-mini Wireless Vacuum Gauge, and Wireless Temperature Clamps.

2. Ihirangi mokete

Manatokona kei roto katoa nga mea kei roto i te kete:

  • EMG-40Vpro Digital Manifold Gauge
  • VGW-mini Wireless Vacuum Micron Gauge
  • 2 x Wireless Temperature Clamps (IPT-01)
  • 2 x Wired Temperature Clamps
  • Refrigerant Hoses (set)
  • USB Cable for charging/data export
  • Pukapuka Kaiwhakamahi (tenei tuhinga)

3. Nga waahanga matua

  • Pūnaha Whakauru: Combines digital manifold, wireless vacuum gauge, and wireless temperature clamps for comprehensive HVAC diagnostics.
  • Mata Paa Ataata: Provides clear data and graph displays for real-time monitoring of vacuum, pressure, and temperature.
  • Wireless Vacuum Measurement: VGW-mini measures vacuum from 19,000 Microns down to 0 Micron with high accuracy.
  • Paemahana Ahokore Clamps: High-precision Type-T thermocouple sensors offer reliable measurements from -40°F to 302°F (-40°C to 150°C).
  • Hononga Nihokikorangi: Remote monitoring via the Elitech Tools App with a range up to 328 feet (100 meters).
  • Data Logging & Export: Records up to 100,000 data points, exportable via USB.
  • Whakahoutanga OTA: Firmware updates for the manifold and wireless clamps are available via the mobile app.
  • Tautoko Refrigerant: Supports 88 types of refrigerants.
  • Intelligent Vacuum Leakage Judgment: Assists in identifying system leaks.
  • Utu Pawera: Improves accuracy for tightness testing results.
Elitech EMG-40Vpro features including OTA updates, intelligent vacuum leakage, offline data, temperature compensation, 88 refrigerants, and 5-inch touch screen.

Whakaatu 3.1: Neke Atuview of EMG-40Vpro's integrated features.

Elitech EMG-40Vpro displaying real-time data and showing data export capabilities.

Figure 3.2: Real-time data monitoring and offline data export functionality.

Elitech VGW-mini wireless vacuum gauge displaying vacuum value and water vapor status.

Figure 3.3: Wireless vacuum measurements with the VGW-mini.

Elitech wireless digital temperature clamp IPT-01 highlighting its high precision sensor, OTA update, wide range, real-time measurement, history data viewing, and data waveform display.

Figure 3.4: Features of the IPT-01 Wireless Digital Temperature Clamp.

Elitech Tools App interface showing historical data analysis from the wireless temperature clamp.

Whakaahua 3.5: Viewing and analyzing historical data via the Elitech Tools App.

Elitech Tools App interface demonstrating OTA firmware updates for the device.

Figure 3.6: OTA firmware updates through the Elitech Tools App.

4. Tatūnga

4.1 Tautuhinga Wae

Te tuara me te taha view of Elitech EMG-40Vpro manifold showing power button, magnetic hook, high/low temp interfaces, USB-C charging port, and 1/4 inch and 3/8 inch SAE valves.

Figure 4.1: EMG-40Vpro Manifold Component Overview.

Familiarize yourself with the manifold's ports and controls:

  • Pātene Hiko: Kei te taha.
  • Matau aukume: For convenient mounting.
  • High/Low Temp Interface: Ports for wired temperature clamps.
  • Tauranga Whakatau USB-C: For charging the manifold and data export.
  • Takirere: 1/4" SAE and 3/8" SAE ports for refrigerant hoses.

4.2 Whakataki Tuatahi

Before first use, fully charge the EMG-40Vpro manifold and the VGW-mini vacuum gauge using the provided USB-C cable. Connect the cable to the respective charging ports and a suitable USB power adapter (not included).

4.3 Whakauru Whakauru

Download the Elitech Tools App from the App Store (iOS) or Google Play Store (Android) on your mobile device. This app is essential for remote monitoring, data analysis, and firmware updates.

4.4 Hononga Wae

  1. Refrigerant Hoses: Connect the appropriate refrigerant hoses to the manifold's 1/4" SAE and 3/8" SAE ports as required for your HVAC system.
  2. VGW-mini Vacuum Gauge: Screw the VGW-mini directly onto a service port or a manifold port for vacuum measurements. Ensure a tight seal.
  3. Te pāmahana Clamps:
    • Wireless Clamps (IPT-01): Power on the clamps. They will automatically attempt to connect to the manifold or the Elitech Tools App via Bluetooth. Attach them securely to the refrigerant lines.
    • Wired Clamps: Plug the wired temperature clamps into the designated high and low temperature interfaces on the manifold. Attach them securely to the refrigerant lines.

5. Nga Tohutohu Whakahaere

5.1 Kei te Hiko / Weto

Press and hold the power button on the side of the manifold to turn the device on or off. The touch screen will illuminate upon startup.

5.2 Te whakatere i te Atanga

The EMG-40Vpro features a 5-inch touch screen. Navigate through menus and settings by tapping icons and swiping. The main screen displays real-time pressure, temperature, and vacuum data.

5.3 Bluetooth Connectivity (App)

  1. Me mohio kei te whakahohea te Nihokikorangi i runga i to taputapu pūkoro.
  2. Open the Elitech Tools App.
  3. The app will scan for nearby Elitech devices. Select your EMG-40Vpro manifold and IPT-01 clamps from the list to connect.
  4. Ina hono, ka taea e koe view real-time data, configure settings, and initiate data recording from the app.

5.4 Selecting Refrigerant

On the manifold's touch screen, navigate to the refrigerant selection menu. Choose the appropriate refrigerant type for the system you are working on from the list of 88 supported refrigerants.

5.5 Te Mahi Ine

  1. Pēhanga: Once hoses are connected to the system, open the manifold valves as needed to measure high and low side pressures. Readings will display on the screen.
  2. Mamao: With the VGW-mini connected, initiate a vacuum process. The gauge will display micron readings, allowing you to monitor evacuation progress.
  3. Te pāmahana: Ensure temperature clamps are properly attached to the refrigerant lines. The manifold will display the measured temperatures.

5.6 Data Recording and Export

The EMG-40Vpro can record up to 100,000 data points. To start recording, use the on-screen controls or the Elitech Tools App. To export data, connect the manifold to a computer via the USB-C cable. The device will appear as a storage device, allowing you to transfer recorded data files.

6. Tiaki

6.1 Te horoi

Wipe the manifold, vacuum gauge, and clamps ki te ngohengohe, damp cloth. Do not use abrasive cleaners or solvents. Ensure all ports are free of debris before and after use.

6.2 Rokiroki

Store the device and its accessories in a clean, dry environment, away from extreme temperatures and direct sunlight. Ensure all components are fully charged before long-term storage.

6.3 Whakahoutanga Firmware

Regularly check for firmware updates via the Elitech Tools App to ensure optimal performance and access to the latest features. Follow the in-app instructions for updating.

7. Te Raru

PutangaTake peaRongoā
Kaore te taputapu i te hikoPūhiko iti; Kaore i tika te pehi i te paatene hikoCharge the device; Press and hold the power button for 3 seconds
Cannot connect to Elitech Tools AppBluetooth off; Device out of range; App not updatedEnsure Bluetooth is on; Move device closer to phone; Update app to latest version
Inaccurate pressure/temperature readingsLoose connections; Sensor obstruction; Incorrect refrigerant selectedCheck hose/clamp connections; Ensure sensors are clean; Verify correct refrigerant in settings
VGW-mini vacuum gauge not readingLow battery; Loose connection; Sensor contaminatedCharge VGW-mini; Ensure tight connection to service port; Clean sensor if necessary
Data export not workingUSB cable issue; Incorrect connection modeTry a different USB cable; Ensure device is recognized as a storage device on computer

8. Whakatakotoranga

Elitech EMG-40Vpro dimensions and technical specifications including pressure, vacuum, and temperature measurement ranges and units.

Figure 8.1: EMG-40Vpro Dimensions and Key Specifications.

  • Awhe Ine Pehe: -14.5 ki te 800 psi
  • Wae Pehe: psi, kg/cm², cmHg, inHg, bar, kPa, MPa
  • Vacuum Measurement Range: 1 ki te 19,000 microns
  • Wae Korehau: micron, inHg, Torr, psia, mbar, mTorr, Pa, kPa
  • Huringa Whanganga Hoe: -40°F ki te 302°F (-40°C ki te 150°C)
  • VGW-mini Vacuum Gauge Accuracy: ±10% or ±10 Micron
  • Paemahana Ahokore Clamp Tika: ±0.9°F (at 77°F)
  • Hononga Ahokore: Bluetooth, up to 328 feet (100 meters) range
  • Rokiroki Raraunga: Tae atu ki te 100,000 nga tohu raraunga
  • Whakaatu: 5-inihi Mata Pa
  • Dimensions (Manifold): Approximately 10 inches (H) x 6.3 inches (W) x 1.8 inches (D)
  • Weight (Manifold): Tata ki te 3.6 lbs

9. Pūtāhui me te Tautoko

Elitech products are designed for reliability and performance. For specific warranty details, please refer to the warranty card included with your product or visit the official Elitech website. For technical support, troubleshooting assistance, or service inquiries, please contact Elitech customer service through their official channels.

Elitech Technology Inc.
Webpae: www.elitechustore.com (Exoample, please refer to actual Elitech website for support contact information)

Tuhinga e pa ana - EMG-40Vpro

Preview Elitech Intelligent Digital Manifold Manual Kaiwhakamahi
Ko te pukapuka kaiwhakamahi matawhānui mo te Elitech Intelligent Digital Manifold, e kapi ana i nga tauira EMG-20V me EMG-40V. Akohia nga ahuatanga o te hua, nga whakaritenga, te mahi, te tiaki, me te rapu raru mo nga punaha HVAC/R.
Preview Pukapuka Kaiwhakamahi mō te Ine Mamati Atamai Elitech MS-100 PLUS
He pukapuka kaiwhakamahi whānui mō te Elitech MS-100 PLUS Smart Digital Manifold Gauge, e kapi ana i te whakaurunga hua, ngā tohutohu haumaru, me ētahi atuview, ngā mahi pātene, ngā tawhā hangarau, me ngā aratohu whakahaere tere mō ngā pūnaha whakamatao me te HVAC.
Preview Elitech MS-100 Digital Manifold Gauge Manual
Te pukapuka a te kaiwhakamahi mo te Elitech MS-100 Digital Manifold Gauge, e whakaatu ana i ona ahuatanga, mahi, whakaritenga, me te tiaki.
Preview Ine Mamati Elitech MS-100: Ngā Āhuatanga, te Mahi, me ngā Whakatakotoranga
He aratohu whānui mō te Elitech MS-100 Digital Manifold Gauge, e kapi ana i ōna āhuatanga, te tere o te whakahaere, ngā whakaritenga hangarau, ngā whakatūpato, me ngā taipitopito hua mō ngā pūnaha HVAC me te pouaka whakamātao.
Preview Pukapuka Kaiwhakamahi mō te Ine Mamati a Elitech MS Series
Pukapuka kaiwhakamahi mō te ine ine matihiko Elitech MS Series, e kapi ana i te whakaahuatanga hua, whānui atu i teview, ngā mahi pātene, ngā whakatakotoranga, te aratohu tīmatanga tere, ngā mahi whakahaere, ngā tono atamai, me te tiaki.
Preview Pukapuka Kaiwhakamahi me ngā Whakatakotoranga mō te Ine Mamati a Elitech MS-800 Series
He pukapuka kaiwhakamahi whānui mō te taputapu manifold mamati Elitech MS-800 Series, e kapi ana i te whakaurunga hua, ngā aratohu haumaru, te tiaki taiao, ngā whakatakotoranga taipitopito, me ngā aratohu whakahaere tere mō ngā inenga pēhanga me te pāmahana, ngā whakamātautau pēhanga pupuri, me te utu hauhautanga mō ngā pūnaha HVAC me te pouaka whakamātao.