ED-PAC3020 EDATEC Ahumahi Aunoa me nga Mana Whakahaere

Whakatakotoranga
- Ingoa Hua: ED-PAC3020
- Kaihanga: EDA Technology Co., Ltd
- Te Ra Whakaputa: Akuhata 1, 2025
- Pūmanawa Papatono: CODESYS V3.5 SP19
- Whirihoranga Mahara: 2GB DDR + 128GB SSD or 8GB DDR + 256GB SSD
- Atanga: HDMI, USB, Ethernet, RS232, RS485
Nga Tohutohu Whakamahi Hua
- Ka mutuview:
- The ED-PAC3020 is a real-time CODESYS programmable automation controller suitable for industrial control and IoT fields. It comes pre-installed with a multi-core CODESYS runtime and offers different memory configurations based on user requirements.
- Pūmārō:
- The device features commonly used interfaces such as HDMI, USB, Ethernet, RS232, and RS485. It integrates an RTC and supports connection to remote EtherCAT-based I/O modules.
- Introduction to CODESYS Software:
- The product supports CODESYS V3.5 SP19 and later versions for programming and control.
- Taupānga Whatunga:
- The device offers EtherCAT, Ethernet, RS485, and RS232 interfaces for multi-layer network communication to meet diverse application requirements.
Paewhiri Mua:
- Tauranga RS232: Ka whakamahia hei hono i nga taputapu mana tuatoru.
- Green UART indicators: Check the communication status of UART port.
- Tohu hiko Whero: Ka tohu i te mana hiko o te taputapu.
- Green system status indicator: Shows system read/write operations status.
- Putanga Ororongo (HPO): Putanga ororongo stereo.
- Whakauru Ororongo (LINE IN): Ka tautoko i te urunga ororongo tiwharewha.
- RS-485 port: Used to connect third-party control equipment.
- USB 2.0 tauranga: Tautoko ake ki te 480Mbps tere tuku.
Pukapuka Taputapu
- Ko tenei upoko e whakaatu ana i te huaview, pūmanawa CODESYS, tono whatunga, rārangi tākai, ahua, pātene, tohu me atanga.
Ka mutuview
- The ED-PAC3020 is a real-time CODESYS programmable automation controller, pre-installed by default with a multi-core CODESYS runtime. Depending on the application scenario and user requirements, it offers programmable logic system configurations with either 2GB DDR + 128GB SSD or 8GB DDR + 256GB SSD.
WHAKATOKANGA
- The ED-PAC3020 device comes pre-installed with a valid CODESYS license by default. Reinstalling the operating system will invalidate the CODESYS license. Do not attempt to install the OS on your own.
- Ko te ED-PAC3020 e whakarato ana i nga atanga e whakamahia nuitia ana penei i te HDMI, USB, Ethernet, RS232, me RS485, e whakauru ana i te RTC, me te whakamahi tuatahi i roto i te whakahaere ahumahi me nga mara IoT.
- The ED-PAC3020 supports connection to remote EtherCAT-based I/O modules (e.g., couplers, DI, DO, AI, AO) via an EtherCAT network.
- The device integrates the CODESYS Control Runtime System, supporting IEC 61131-3 programming standards and industrial communication protocols like EtherCAT and Modbus TCP.
Users can optionally enable additional functionalities by licensing features such as:
- TargetVisu
- WebVisu Softmotion
- CNC + Robotics
- EtherCAT Kaiwhakaako
- Modbus TCP Master
- OPC UA Tūmau

E waatea ana nga whirihoranga ritenga hei whakatutuki i nga whakaritenga tono motuhake.
Introduction to CODESYS Software
- CODESYS (Controller Development System) is an open industrial automation software development platform that provides a full-stack solution for programming, debugging, and maintaining programmable logic controllers (PLCs), industrial PCs (IPCs), and embedded control systems.
- Compliant with the IEC 61131-3 international standard, it supports complex logic control, multi-axis motion control, industrial communication protocol integration, and real-time data processing.
- It is widely used in smart manufacturing, energy management, logistics automation, and other industrial fields.
Nga waahanga matua o CODESYS:
- Standardized Programming Language Support
- Full compatibility with the IEC 61131-3 programming languages:
- Hoahoa arawhata (LD)
- Hoahoa Paraka Mahi (FBD)
- Kuputuhi Hangaia (ST)
- Rarangi Tohutohu (IL)
- Tūtohi Mahi Rangatahi (SFC)
- Supports Object-Oriented Programming (OOP) extensions for large-scale complex projects.
- Full compatibility with the IEC 61131-3 programming languages:
- Cross-Platform Development & Deployment
- Development Environment: Compatible with Windows and Linux operating systems, offering a unified engineering interface.
- Target Systems: Deployable on 2,000+ industrial controller hardware platforms, including ARM/X86 architectures.
- Modular Engineering Libraries
- Prebuilt Libraries: Include industrial protocol stacks (Modbus/TCP, OPC UA, EtherCAT) and advanced control modules (PID control, CNC interpolation algorithms).
- Custom Libraries: Support encapsulation and reuse of Function Blocks and POUs (Program Organization Units).
- Visual Debugging & Diagnostic Tools
- Real-time monitoring of variables, I/O mapping, and task execution status with waveform analysis.
- Advanced debugging tools: breakpoints, step-by-step execution, and cross-referencing for rapid fault diagnosis.
- Integrated HMI development tools for seamless SCADA system integration.
- Ko te ED-PAC3020 e tautoko ana i te CODESYS V3.5 SP19 me nga putanga o muri mai.
Taupānga Whatunga
- The ED-PAC3020 features EtherCAT, Ethernet, RS-485 and RS-232 interfaces, enabling multi-layer network communication to meet diverse application requirements across various scenarios. A typical application topology is illustrated in the figure below:

Rarangi Tapaki
- 1 x ED-PAC3020 Unit
- 4 x Pads
Te ahua
- Introducing the functions and definitions of the interfaces on each panel.
Paepae Mua
Te whakauru i nga momo atanga o mua me nga whakamaramatanga.
| NO. | Mahi Whakamaramatanga |
| 1 x RS232 port, 3-Pin 3.5mm pitch phoenix terminal, which is used to connect the third-party control
taputapu. |
|
| 2 | 2 x tohu UART matomato, e whakamahia ana hei tirotiro i te mana korero o te tauranga UART. |
| 3 | 1 x tohu hiko whero, e whakamahia ana ki te tirotiro i te mana o te taputapu hiko me te hiko. |
| 4 | 1 x tohu mana pūnaha matomato, e whakamahia ana ki view te mana o nga mahi panui/tuhi a te punaha. |
| 5 | 1 x Putanga Ororongo (HPO), 3.5mm te hono jack ororongo (matomato), putanga ororongo tiwha. |
| 6 | 1 x Whakauru Ororongo (LINE IN), 3.5mm te hono jack ororongo (whero), e tautoko ana i te urunga ororongo tiwharewha. |
|
7 |
1 x RS485 tauranga, 3-Pin 3.5mm pitch phoenix terminal, e whakamahia ana hei hono i nga taputapu mana tuatoru. |
| 8 | 2 x USB 2.0 tauranga, Momo-A tūhono, ia hongere tautoko ake ki te 480Mbps tere tuku. |
| 9 | 2 x USB 3.0 tauranga, Momo-A tūhono, ia hongere tautoko ake ki 5Gbps tere tuku. |
|
10 |
1 x Ethernet interface (10/100/1000M auto-negotiation), RJ45 connector, EtherCAT communication interface for connecting to EtherCAT networks, with PoE (Power over Ethernet) support. |
Paewhiri Whakamuri
- Te whakauru i nga momo atanga paewhiri muri me nga whakamaramatanga.

| NO. | Mahi Whakamaramatanga |
| 1 | 1 x pātene mana, e whakamahia ana hei whakakā me te whakaweto i te taputapu. |
|
2 |
1 x mokamoka kāri SD Micro, kua rahuitia mo te whakamahi a meake nei.
Tuhipoka: Ka puta te taputapu mai i te SSD ma te taunoa. Kua rahuitia tenei mokamoka kaari Micro SD mo te kaha roha. |
Paewhiri taha
- Te whakauru i nga momo atanga paewhiri taha me nga whakamaramatanga.

| NO. | Mahi Whakamaramatanga |
| 1 | 1 x tāuru DC, tūhono USB Momo-C, e tautoko ana i te whakauru hiko 5V 5A. |
| 2 | 2 x tauranga HDMI, hononga Micro HDMI, ka taea te hono i tetahi whakaaturanga me te tautoko i te 4K 60Hz |
Pātene
- The ED-PAC3020 includes a ON/OFF button, and the silkscreen is “ON/OFF”. If you run Raspberry Pi Desktop, you can initiate a clean shutdown by briefly pressing the power button. A menu will appear asking whether you want to shutdown, reboot, or logout.

TIP
- Mena kei te whakahaere koe i te Papamahi Raspberry Pi, ka taea e koe te pehi i te paatene hiko kia rua nga wa i roto i te raupapa tere ki te kati.
Tohutohu
- Ko tenei waahanga e whakamarama ana i te mana me nga tikanga o nga tohu kua whakauruhia ki roto i te taputapu ED-PAC3020.
| Indicator | Tūnga | Whakaahuatanga |
|
PWR |
On | Kua whakahikohia te taputapu. |
|
Kimo |
He rereke te tuku hiko o te taputapu, me whakamutu tonu te tuku hiko. | |
| Wehe | Kaore te taputapu i te hiko. | |
|
ACT |
Kimo |
The system started successfully and is reading and writing data. |
| Indicator | Tūnga | Whakaahuatanga |
|
Wehe |
The device is not powered on or does not read and write data. | |
| COM1~COM2 | Ki/Kemo | Kei te tukuna nga korero |
|
Wehe |
The device is not powered on or there is no data transmission. | |
| Yellow indicator of Ethernet port | On | Kei te ahua noa te hononga Ethernet. |
| Kimo | The Ethernet connection is abnormal. | |
| Wehe | Ko te hononga Ethernet kaore i te whakarite. | |
| Green indicator of Ethernet port | On | Kei te ahua noa te hononga Ethernet. |
| Kimo | Kei te tukuna nga raraunga ma runga i te tauranga Ethernet. | |
| Wehe | Ko te hononga Ethernet kaore i te whakarite. |
TIP
- Ko te mahi o te tohu PWR / ACT i runga i te Raspberry Pi 5 kua whakawhitia ki nga tohu PWR me ACT motuhake ma te taunoa, na ka mau tonu te tohu PWR / ACT i muri i te hiko o te taputapu.
Atanga
- Te whakauru i te whakamaramatanga me te mahi o ia atanga i roto i te hua.
Atanga Mana
- Kei roto i te taputapu ED-PAC3020 tetahi atanga whakauru hiko, e whakamahi ana i te hononga USB Momo-C kua tapaina "PWR IN" me te tautoko i te whakauru hiko 5V 5A.
TIP
- Kia pai ake ai te mahi a Raspberry Pi 5, ka tūtohuhia kia whakamahia he taputapu hiko 5V 5A.
- 1.8.2 1000M Atanga Itarangi (EtherCAT)
- The ED-PAC3020 device includes one auto-negotiating 10/100/1000M Ethernet interface with an RJ45 connector featuring status LEDs, labeled as ”
“. This interface serves as an EtherCAT communication port for connecting to EtherCAT networks and supports PoE (Power over Ethernet) power delivery.
Atanga HDMI
- Kei roto i te taputapu ED-PAC3020 nga hononga HDMI 2 ma te whakamahi i nga hononga Micro HDMI, kua tapaina "HDMI", mo te hono i nga whakaaturanga HDMI. Ka tautokohia e enei atanga te whakaputanga ataata ki te 4Kp60.
TIP
- Some third-party Micro HDMI cables may have shorter Micro HDMI connectors, which could cause connection issues. It is recommended to use the official Raspberry Pi Micro HDMI to Standard HDMI cable for optimal compatibility.
USB 2.0 Atanga
- The ED-PAC3020 device includes 2 USB 2.0 interfaces with standard Type-A connectors, labeled as “
“. These interfaces support connecting standard USB 2.0 peripherals and offer a maximum transfer rate of 480Mbps.
USB 3.0 Atanga
- The ED-PAC3020 device includes 2 USB 3.0 interfaces with standard Type-A connectors, labeled as “
“. These interfaces support connecting standard USB 3.0 peripherals and offer a maximum transfer rate of 5Gbps.
Atanga RS232
- The ED-PAC3020 device includes 1 RS232 interface with a 3-Pin 3.5mm pitch Phoenix terminal, labeled “TX/RX/GND”.
Whakatakoto Pin
- Ko nga titi kapeka kua tautuhia e whai ake nei:
|
Pin ID | Ingoa Pin |
| 1 | TX | |
| 2 | RX | |
| 3 | GND |
Ko te atanga RS232 e rite ana ki nga ingoa titi e whai ake nei i runga i te Pi5:
| Waitohu | Pi5 GPIO Name | Pi5 Pin Ki waho |
| TX | GPIO4 | UART3_TXD |
| RX | GPIO5 | UART3_RXD |
Ko te raupapa waea waea RS232 e whai ake nei:
Atanga RS485
- The ED-PAC3020 device includes 1 RS485 interface with a 3-Pin 3.5mm pitch Phoenix terminal, labeled “A/B/GND”.
Whakatakoto Pin
- Ko nga titi kapeka kua tautuhia e whai ake nei:
|
Pin ID | Ingoa Pin |
| 1 | A | |
| 2 | B | |
| 3 | GND |
Ko te atanga RS485 e rite ana ki nga ingoa titi e whai ake nei i runga i te Pi5:
| Waitohu | Pi5 GPIO Name | Pi5 Pin Ki waho |
| A | GPIO12 | UART5_TXD |
| B | GPIO13 | UART5_RXD |
Hononga taura
- Ko te raupapa waea waea RS485 e whai ake nei:

RS485 Whakamutua te Whirihoranga Whakatairanga
- The ED-PAC3020 device includes 1 RS485 interface.
- A 120Ω termination resistor is reserved between the A and B lines of the RS485 circuit. Inserting a jumper cap enables this termination resistor.
- By default, no jumper is installed, rendering the 120Ω termination resistor inactive. The termination resistor is located at J7 on the PCBA (printed circuit board assembly).
TIP
- The device case must be opened to inspect the 120Ω termination resistor.
Whakauru Ororongo
- Kei roto i te taputapu ED-PAC3020 1 atanga whakauru ororongo (LINE IN), he 3.5mm jack ororongo whero, kua tapaina hei " ", e tautoko ana i te whakaurunga tiwharewha.
Putanga Ororongo
- The ED-PAC3020 device includes 1 audio output interface (HPO), a green 3.5mm audio jack, labeled as ”
“, which supports stereo output.
Te Tāuta i te Pūrere
- Ko te taputapu ED-PAC3020 he mea hoahoa mo te tuunga papamahi ma te taunoa me te tautoko i te whakapuru pakitara me te ED-ACCBKT-L3020 taiapa taiepa mai i ta maatau kamupene.
TIP
- The ED-PAC3020 packaging box does not include the ED-ACCBKT-L3020 by default. Users must purchase it separately.
Whakaritenga:
- Prepared a Phillips-head screwdriver.
- Obtained the ED-ACCBKT-L3020 wall-mount bracket.
Hipanga:
- Use a Phillips screwdriver to unscrew the four M2.5 screws on the side of the ED-IPC3020 counterclockwise.

- Align the left and right brackets of the ED-ACCBKT-L3020 with the screw holes on both sides of the ED-PAC3020, insert the four M2.5*6 screws, and tighten them clockwise with a Phillips screwdriver to secure the ED-ACCBKT-L3020 to the sides of the ED-PAC3020.

- Based on the spacing and diameter of the wall-mounting screw holes of the ED-ACCBKT-L3020 left and right brackets (refer to the diagram below), drill holes in the wall accordingly, then proceed with wall-mounted installation of the device.
Waeine: mm - Tolerance: 0.5-6±0.05, 6-30±0.1, 30-120±0.15
Ahu

Te Whakaoho i te Pūrere
- Kei roto i tenei upoko nga tikanga motuhake mo te hono i nga taura me te hiko i runga i te taputapu.
Hononga taura
- This section describes the procedures for connecting cables to the device.
Whakaritenga:
- Obtained fully functional accessories such as a switch, monitor, mouse, keyboard, I/O expansion module, and power adapter.
- Available functional network connection.
- Available functional cables: HDMI cable and Ethernet cable.
Hoahoa hoahoa o nga taura hono:
- Tena tirohia te 1.8 Atanga mo te whakamaramatanga titi o ia atanga me te tikanga motuhake mo te waea.
TIP
- Some third-party Micro HDMI cables may have shorter Micro HDMI connectors, which could cause connection issues. It is recommended to use the official Raspberry Pi Micro HDMI to Standard HDMI cable for optimal compatibility.

Booting The System For The First Time
- Once the ED-PAC3020 is connected to power, the system will begin to boot up.
- Red PWR indicator: Lights up to indicate the device is receiving power.
- Green ACT indicator: Blinks to signal normal system startup. The Raspberry Pi logo will then appear in the upper-left corner of the screen.
TIP
- The default username is pi, the default password is raspberry.
Raspberry Pi OS (Papamahi)
- Mena kei te wheketere te taputapu me te OS Papamahi, ka peke tika ki te atanga papamahi i te tiimatanga, penei i te ahua i raro nei.

Raspberry Pi OS (Lite)
- Mena he wheketere te taputapu me te Lite OS, ka uru aunoa ma te whakamahi i nga tohu taunoa i muri i te tiimatanga. Ko te ahua i raro nei e tohu ana kua eke te punaha.

CODESYS Programming
- Kei tenei upoko nga korero mo nga mahi motuhake mo te whakamahi CODESYS.
WHAKATOKANGA
- The ED-PAC3020 device comes pre-installed with a valid CODESYS license by default. Reinstalling the operating system will invalidate the CODESYS license. Do not attempt to install the OS on your own.
- CODESYS Software Download and Installation
TIP
- The installed CODESYS IDE version must be 3.5.19 or higher, and the PC operating system must be Windows 10 or Windows 11 (64-bit recommended).
- Download the installation package from the official CODESYS webpae. Ko te tango URL is https://store.codesys.com/de/ (https://store.codesys.com/de/).
-
TIP
-
When downloading from the CODESYS official webpae mo te wa tuatahi, me rehita tuatahi koe me te takiuru ki to putea.
- Right-click the downloaded installer and select “Run as administrator” from the context menu. Click “Install” in the opened installation interface, and keep the default configuration during the installation process.

- After the installation is complete, click “Finish” to close the installation interface.

Obtaining and Installing Device Description File
- I mua i te hono atu ki te taputapu ma te CODESYS, me tango me te whakauru i te whakaahuatanga taputapu file tuatahi.
Obtaining Device Description File
TIP
- The device’s default Ethernet port IP address is 192.168.0.100. To modify it, refer to Configuring Ethernet IP.
Whakaritenga:
- A CODESYS-authorized ED-PAC3020 is available.
- A functional Ethernet cable is available.
- A Windows PC is prepared, with its IP address configured to the same subnet as the device. For exampe, ki te IP o te pūrere (1000M tauranga Ethernet) ko 192.168.0.100 , whakaturia te IP o te PC ki 192.168.0.99 .
Hipanga:
- Connect the device’s Ethernet port to the PC via an Ethernet cable, then power on the device.
- Enter http://192.168.0.100:8100 in the PC’s web pūtirotiro ki te uru ki te atanga "PLC Setting".
- In the “Device Info” section, click the “[Download] Device Description File” button to download the corresponding “.xml” format device description file.

TIP
- Also available directly in the document ED-PAC3020 Device File (https://vip.123pan.cn/ 1826505135/17964309) .
Installing Device Description File
Whakaritenga:
- A PC installed with CODESYS software version V3.5 SP19 (64-bit).
- An ED-PAC3020 device with a valid CODESYS license and its corresponding device description file.
- Connect both the PC and ED-PAC3020 to the network, ensuring their IP addresses are within the same subnet.
Hipanga:
- Double-click the CODESYS icon on the PC desktop to open the CODESYS software. From the menu bar, select “Tools” → “Device Repository”.

- In the opened “Device Repository” pane, click “Install”.

- In the pop-up “Install Device Description” pane, select the device description file ki te tāuta me te pāwhiri "Open" ki te haere ki te tāutanga.
- After successful installation, you can verify in the “Device Repository” that the device description file kua pai te taapiri.

Installing Remote I/O Device Description File
Whakaritenga:
- A PC installed with CODESYS software version V3.5 SP19 (64-bit).
- An ED-PAC3020 device with a valid CODESYS license.
- The remote I/O device description fileKua tangohia mai i: Whakamarama I/O Mamao Files (https://vip.123pan.cn/1826505135/16632390).
- Connect the PC, ED-PAC3020, and remote I/O devices to the same switch. Ensure that the IP addresses of the PC, ED-PAC3020, and remote I/O devices are within the same subnet.
Hipanga:
- Double-click the CODESYS icon on the PC desktop to open the CODESYS software. From the menu bar, select “Tools” → “Device Repository”.

- In the opened “Device Repository” pane, click “Install”.

- In the pop-up “Install Device Description” pane, select the I/O device decirption file ki te tāuta me te pāwhiri "Open" ki te haere ki te tāutanga.
- After successful installation, you can verify in the “Device Repository” that the I/O device description file kua pai te taapiri.

Whirihoranga Pūmārō
Whakaritenga:
- A PC installed with CODESYS software version V3.5 SP19 (64-bit).
- The device description files me te whakaahuatanga taputapu I/O mamao files have been installed. Connect the PC, ED-PAC3020, and remote I/O devices to the same switch. Ensure that the IP addresses of the PC, ED-PAC3020, and remote I/O devices are within the same subnet.
Create a New Project and Connect to the Device
Hipanga:
- Power on the ED-PAC3020 and the remote I/O modules. Open the CODESYS software on the PC, select “File” → “New Project” in the menu bar to open the “New Project” pane, and create a standard project.

- Select the installed device description file ka paato "OK".

- Double-click the device, select “Scan Network” on the right, then choose the detected device from the scan results, and click “OK” to confirm.

TIP
- If the device cannot be detected during scanning, manually enter the IP address in the target device settings to connect.
- If a device login prompt appears, log in with your credentials (username and password) or follow the instructions to register a new account.\
As shown in the figure below, this indicates the device is successfully connected.
Adding Remote I/O Modules
Hipanga:
- Right-click “Device” and select “Add Device” in the menu to add the EtherCAT Master.

- Double-click on the EtherCAT Master device to set the source address (Select the EtherCAT port, which corresponds to the device’s eth0 port).

- Patohia te
button to log in to the device. A successful login is shown in the figure below.
- Click on the EtherCAT Master device, select “Scan for Devices” in the right-click menu, and copy all devices to the project after scanning is completed.

- Patohia te
button to log out of the device. - Double-click the slave device, configure the relevant parameters in the right-hand interface, enable “Expert settings”, select “Enable” under Select DC section, and select “Enable Sync0”.

- Patohia te
button to download the program to the device, then click the button to run it. As
shown in the figure below, this indicates a successful operation.
Papatonotanga
- Ko te ex e whai ake neiampe whakaatu ana i nga hotaka mahi ma te whakamahi i tetahi ahuatanga whakawaehere motuhake.
Tukanga Papatono

Papatono Example
- Complete the development and debugging of a program for a timed blinking LED using a PNP-type 8-channel digital output (DO) module.
Whakaritenga:
- A standard project has been created.
- Hardware configuration has been completed.
- A 24V compact LED lamp has been connected to the first output port of the remote DO (Digital Output) module.
Nga hikoinga
- Double-click the DO module, select “Module I/O Mapping” → “Output” in the right-hand interface, and view nga wahitau o nga tauranga whakaputa katoa. Ka rite ki te whakaahua i raro nei, ko te wahitau o te tauranga putanga tuatahi ko %QX18.0 .

- Write the program code as follows:

- After completing the program, click ”
” to compile it and ensure there are no errors.
- Click Login to download the program to the device, then click Run to observe the LED blinking every 0.5 seconds.

Te Mahi me te Tiaki
- I muri i te tango i te papatono ki te taputapu, ka taea e koe te mahi i nga mahi Whakahaere me te Kati.
| Tūnga | Nga Mahi |
| Whakahaere Papatono | In the main menu of the software interface, click the Login button. |
| Kati te Papatono | In the main menu of the software interface, click the stop button. |
Whirihora i te Pūnaha
- Ko tenei upoko e whakaatu ana me pehea te whirihora i te punaha.
WHAKATOKANGA
- The ED-PAC3020 device comes pre-installed with a valid CODESYS license by default. Reinstalling the operating system will invalidate the CODESYS license. Do not attempt to install the OS on your own.
- Te kimi IP Pūrere
- Whakauru Mamao
- Whirihora Wi-Fi
- Te whirihora IP Itarangi
- Configuring Bluetooth.
- Whirihorahia te Buzzer
- The buzzer is controlled using GPIO6.
- Execute the following command to turn on the buzzer:

- Whirihora RTC
- Whirihora Tauranga Rangatū
- Ko tenei upoko e whakaatu ana i te tikanga whirihoranga o RS232 me RS485.
Installing Picocom Tool
- I roto i te taiao Linux, ka taea e koe te whakamahi i te taputapu picocom ki te patuiro i nga tauranga rangatū RS232 me RS485.
- Whakamahia te whakahau e whai ake nei hei whakauru i te taputapu picocom.

- 5.8.2 Whirihorahia te RS232
Kei roto i te ED-PAC3020 te atanga 1 RS232, me tona tauranga COM me te taputapu files kua whakarārangihia ki te ripanga i raro nei:
| Tau of RS485 Tauranga | E rite ana COM Tauranga | E rite ana Pūrere File |
| 1 | COM2 | /dev/com2 |
- Input commands as needed to control external device.
Configuring RS485
- The ED-PAC3020 contains 1 RS-485 interface, and its corresponding COM port and device files kua whakarārangihia ki te ripanga i raro nei:
| Tau of RS485 Tauranga | E rite ana COM Tauranga | E rite ana Pūrere File |
| 1 | COM2 | /dev/com2 |
Whakaritenga:
The RS485 ports of ED-PAC3020 has been connected with external device. Steps:
- Execute the following command to open the serial port com2, and configure the serial port baud rate to 115200.

- Input commands as needed to control external device.
Whirihora Ororongo
- Whirihora Ororongo
- CODESYS License Management
- Ko te taputapu ED-PAC3020 ka tae mai i mua i te whakauru me te raihana CODESYS ma te taunoa. Ka taea e koe te whakahoki me te whakahoki i te raihana ma te uru atu ki te atanga "PLC Setting".
License Backup
Whakaritenga:
- A Windows PC has been set up with an IP address in the same subnet as the device. For exampe, ki te IP o te pūrere (1000M tauranga Ethernet) ko 192.168.0.100 , whakaturia te IP o te PC ki 192.168.0.99 .
- A functioning Ethernet cable has been prepared.
Hipanga:
- Connect the device’s 1000M Ethernet port to the PC via an Ethernet cable, then power on the device.
- Enter http://192.168.0.100:8100 in the PC’s web pūtirotiro ki te uru ki te atanga "PLC Setting".
- In the “Codesys License Management” interface, click “Backup License” to download the license file ka tiaki i te rohe.

TIP
- The backed-up license file ka taea anake te whakahoki mai i runga i te taputapu kotahi.
License Restore
Whakaritenga:
- A Windows PC has been set up with an IP address in the same subnet as the device. For exampe, ki te IP o te pūrere (1000M tauranga Ethernet) ko 192.168.0.100 , whakaturia te IP o te PC ki 192.168.0.99 .
- A functioning Ethernet cable has been prepared.
- The backed-up license file kua whiwhi.
Nga hikoinga
- Connect the device’s 1000M Ethernet port to the PC via an Ethernet cable, then power on the device.
- Enter http://192.168.0.100:8100 in the PC’s web pūtirotiro ki te uru ki te atanga "PLC Setting".
- In the “Codesys License Management” interface, click “Restore License”.

- As prompted, select the obtained license file under a custom path.
- After a successful License Restore, a 100% progress bar will be displayed in the right-hand panel.

- Open the device’s terminal command pane, execute the following command, and restart the device.

Pātai Auau
Q: Ka taea e au te whakauru ano i te punaha whakahaere i runga i te ED-PAC3020?
A: Reinstalling the operating system will invalidate the CODESYS license that comes pre-installed by default. It is advised not to attempt installing the OS on your own.
Q: He aha nga paerewa kaupapa e tautokohia ana e te ED-PAC3020?
A: The device supports IEC 61131-3 programming standards and industrial communication protocols like EtherCAT and Modbus TCP.
Tuhinga / Rauemi
![]() |
EDA ED-PAC3020 EDATEC Ahumahi Aunoa me nga Mana Whakahaere [pdf] Pukapuka Kaiwhakamahi ED-PAC3020 EDATEC Ahumahi Aunoa me nga Mana Whakahaere, ED-PAC3020, EDATEC Ahumahi Aunoa me nga Mana Whakahaere, Ahumahi Aunoa me nga Mana Whakahaere, Aunoa me nga Mana |